When a battery schedule asks for more than it can deliver.

Follow a one-hour SOC calculation, check the energy balance and understand clipped battery dispatch.

Define both the command and the stored energy

A dispatch schedule is a request. The battery can only follow it if power limits, remaining stored energy and site conditions permit. A 1 MW inverter does not guarantee 1 MWh in the next hour if the battery is nearly empty.

Use a synthetic example with 1,000 kW rated power, 2,000 kWh nominal energy, 50% initial SOC, 10% minimum SOC, 90% maximum SOC and 88% round-trip efficiency. Request one hour at full discharge in grid-export mode.

Follow the SOC limit

The lab splits round-trip efficiency symmetrically: charge and discharge efficiency each equal √0.88 = 0.938083. Initial stored energy is 1,000 kWh; minimum stored energy is 200 kWh. Only 800 kWh DC can leave the battery.

AC energy available = (current DC energy − minimum DC energy) × discharge efficiency

800 × 0.938083 = 750.47 kWh AC. Over a one-hour interval, the feasible average discharge is 750.47 kW. The schedule is clipped below its 1,000 kW request and ends at 10% SOC.

With finer intervals, the tool can represent full output for earlier intervals and a partially clipped final interval. A one-hour row is an interval average, not a guarantee of flat power every second.

Check the complete cycle

To restore the 800 kWh removed from storage, AC charging energy is 800 ÷ 0.938083 = 852.80 kWh. The complete cycle returns 750.47 kWh from 852.80 kWh input, giving 88% efficiency. The 102.34 kWh difference is conversion loss in this simplified model.

Compare charge and discharge totals only after accounting for the change between initial and final stored energy. A run beginning with a full battery can export energy that was charged before the displayed study period.

Keep the grid balance consistent

Grid import = load − battery discharge + battery charge

During an illustrative 1,200 kW load, 750.47 kW discharge leaves 449.53 kW of import. At a 400 kW load, export mode produces 350.47 kW of export. Self-consumption mode instead caps discharge at the load.

The built-in load profiles are synthetic. They are useful for learning the tool, but cannot establish your building’s demand savings. Uploaded hourly demand remains hourly information even if you choose 15-minute simulation steps; repeating each hourly value does not recover hidden peaks.

Before relying on a dispatch result

  • Use compatible units and keep SOC limit enforcement enabled for feasible dispatch.
  • Inspect the earliest interval where the requested schedule is clipped.
  • Check initial and final SOC; do not count pre-existing stored energy as recurring revenue.
  • Ensure charge and discharge windows do not unintentionally overlap; the first matching rule takes priority.
  • Validate timestamps, missing readings and units in uploaded profiles.

The lab does not model tariffs, demand-charge ratchets, PV production, degradation cost or temperature-dependent efficiency. A schedule called “solar charging” is still a commanded charge window; the tool does not prove that solar energy is available during that window.

Sources and scope

  1. U.S. DOE: Solar energy and storage basics ↗

    Storage losses and shifting energy in time. The SOC and grid-balance calculations above document this tool’s model.

Reference links provide technical context; the worked examples and interpretation are specific to this guide. No external source certifies these tools.

Put it to work

Try your own assumptions.

BESS dispatch lab ↗Report a calculation or source issue